S.i.t.c Of Fire Detection And Alarm System At Baduria Rural Hospital In Basirhat Hd.rn- 18001353, Project Id-hf212246215s000.
Documents
Unlock the opportunities
Buy This Document-
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Costs
-
EMD
12329.00 -
Document Cost
250.00 -
Estimated Cost
Refer Documents
BOQ Items Total Items : 8 | Total Qty : 1647
# | Item | Quantity | Units |
---|---|---|---|
1 | Supply, Installation,Testing & Commisioning of Micropresssor controlled IP Addressable multisensor detector IP 54 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/Ravel / Honeywell ). | 96 | Nos |
2 | Supply, Installation,Testing & Commisioning of IP Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Cerberus Pro/ Johnson Controls/ Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST/Ravel / Honeywell ). | 7 | Nos |
3 | Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make: Cerberus Pro/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST/ Ravel / Honeywell ). | 7 | Nos |
4 | Supply, Installation,Testing & Commisioning of Micropresssor controlled IP Addressable Heat detector IP 54 ( VDS / UL /ERTL/ LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : Cerberus Pro / Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel / Honeywell ). | 4 | Nos |
5 | Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST/ Ravel/ Agni Suraksha/System Sensor/Honeywell ). | 2 | Nos |