BOQ Items Total Items : 42 | Total Qty : 6805.4
# | Item | Quantity | Units |
---|---|---|---|
1 | Supply, delivery and installation of feeder pillar, 12 Ways, outdoor type fabricated out of 3 mm (approx.) 10 gauge thick sheet steel, 3 phase and neutral, rated at 400 Amps, 415 V, 50 Hz, AC supply having tinned copper bus bars of size 50 x 5 mm (approx.) for phases and 40 x 5 mm (approx.) for neutral, with heat shrinkable insulated sleeves as per colour code, fitted with insulated fuse bases, HRC fuse links etc. as detailed below complete with 1 No. limit switch operated illuminating lamp with holder, 1 No. control board with 16 Amps, MCB, 1 No. 5 pin, 6/16 Amp 230 V combined switch socket flush type, 1 No. 20 W LED lamp 230 V, appropriate sizes of tinned copper extension of pieces for connecting cables ends at back side, 1 No. insulated fuse remover, wedge type and conventional locking arrangements, c.c. foundation, G.I. foundation bolts, nuts & washers, seven tank process with epoxy painting etc. as per the MbPA drawing and specification with number of ways as detailed below. The bottom M. S. angle frame of the cable compartment of the Feeder Pillar shall be made out of 50 X 50 X 6 mm (approx.) M.S. angle and the remaining frame shall be of 40 x 40 x 6 mm(approx.). The overall (approx..) dimensions of the Feeder Pillar are as under: i. Length (height) of the Feeder Pillar including cable compartment but excluding height of the hood = 1800 mm (approx.) ii. Breadth = 2545 mm (approx.) iii. Depth = 350 mm (approx.). a. 3 Nos. incoming ways: - Each way fitted with 3 Nos. 630 A, 415 V insulated fuse bases and 400 A, 415 V, low watt loss HRC fuse links (similar to HN type L&T make). b. 4 Nos. outgoing ways: - Each way fitted with 3 Nos. 400 A, 415 V insulated fuse bases and 315 A, 415 V, low watt loss HRC fuse links (similar to HN type L&T make) c. 5 Nos. outgoing ways: - Each way fitted with 3 Nos. 250 A, 415 V insulated fuse bases and 250 Amp 415 V, low watt loss HRC fuse links (similar to HN type L&T make) d. Godrej Navtal lock 7 lever 65 mm dia with keys in duplicate 1 No. | 2 | Nos. |
2 | Supply, delivery and installation of feeder pillar, 10 Ways, outdoor type fabricated out of 3 mm (approx.) 10 gauge thick sheet steel, 3 phase and neutral, rated at 400 Amps, 415 V, 50 Hz, AC supply having tinned copper bus bars of size 50 x 5 mm (approx.) for phases and 40 x 5 mm (approx.) for neutral, with heat shrinkable insulated sleeves as per colour code, fitted with insulated fuse bases, HRC fuse links etc. as detailed below complete with 1 No. limit switch operated illuminating lamp with holder, 1 No. control board with 16 Amps, MCB, 1 No. 5 pin, 6/16 Amp 230 V combined switch socket flush type, 1 No. 20 W LED lamp 230 V, appropriate sizes of tinned copper extension of pieces for connecting cables ends at back side, 1 No. insulated fuse remover, wedge type and conventional locking arrangements, c.c. foundation, G.I. foundation bolts, nuts & washers, seven tank process with epoxy painting etc. as per the MbPA drawing and specification with number of ways as detailed below. The bottom M. S. angle frame of the cable compartment of the Feeder Pillar shall be made out of 50 X 50 X 6 mm (approx.) M.S. angle and the remaining frame shall be of 40 x 40 x 6 mm(approx.). The overall (approx..) dimensions of the Feeder Pillar are as under: i. Length (height) of the Feeder Pillar including cable compartment but excluding height of the hood = 1800 mm (approx.) ii. Breadth = 2215 mm (approx.) iii. Depth = 350 mm (approx.). a. 3 Nos. incoming ways: - Each way fitted with 3 Nos. 630 A, 415 V insulated fuse bases and 400 A, 415 V, low watt loss HRC fuse links (similar to HN type L&T make). b. 3 Nos. outgoing ways:- Each way fitted with 3 Nos. 400 A, 415 V insulated fuse bases and 315 A, 415 V, low watt loss HRC fuse links (similar to HN type L&T make) c. 4 Nos. outgoing ways :- Each way fitted with 3 Nos. 250 A, 415 V insulated fuse bases and 250 Amp 415 V, low watt loss HRC fuse links (similar to HN type L&T make) d. Godrej Navtal lock 7 lever 65 mm dia with keys in duplicate 1 No. | 16 | Nos. |
3 | Supply, delivery and installation of feeder pillar, 08 Ways, outdoor type fabricated out of 3 mm (approx.) 10 gauge thick sheet steel, 3 phase and neutral, rated at 400 Amps, 415 V, 50 Hz, AC supply having tinned copper bus bars of size 50 x 5 mm (approx.) for phases and 40 x 5 mm (approx.) for neutral, with heat shrinkable insulated sleeves as per colour code, fitted with insulated fuse bases, HRC fuse links etc. as detailed below complete with 1 No. limit switch operated illuminating lamp with holder, 1 No. control board with 16 Amps, MCB, 1 No. 5 pin, 6/16 Amp 230 V combined switch socket flush type, 1 No. 20 W LED lamp 230 V, appropriate sizes of tinned copper extension of pieces for connecting cables ends at back side, 1 No. insulated fuse remover, wedge type and conventional locking arrangements, c. c. foundation, G. I. foundation bolts, nuts & washers, seven tank process with epoxy painting etc. as per the MbPA drawing and specification with number of ways as detailed below. The bottom M. S. angle frame of the cable compartment of the Feeder Pillar shall be made out of 50 X 50 X 6 mm (approx.) M.S. angle and the remaining frame shall be of 40 x 40 x 6 mm(approx.). The overall (approx..) dimensions of the Feeder Pillar are as under: i. Length (height) of the Feeder Pillar including cable compartment but excluding height of the hood = 1800 mm (approx.) ii. Breadth = 1885 mm (approx.) iii. Depth = 350 mm (approx.). a. 2 Nos. incoming ways: - Each way fitted with 3 Nos. 630 A, 415 V insulated fuse bases and 400 A, 415 V, low watt loss HRC fuse links (similar to HN type L&T make). b. 2 Nos. outgoing ways:- Each way fitted with 3 Nos. 400 A, 415 V insulated fuse bases and 315 A, 415 V, low watt loss HRC fuse links (similar to HN type L&T make) c. 4 Nos. outgoing ways :- Each way fitted with 3 Nos. 250 A, 415 V insulated fuse bases and 250 Amp 415 V, low watt loss HRC fuse links (similar to HN type L&T make) d. Godrej Navtal lock 7 lever 65 mm dia with keys in duplicate 1 No. | 29 | Nos. |
4 | Supply and delivery at site of 1100 Volts different size of L.T cable with stranded H2 / H4 grade aluminum conductor XLPE insulated, color coded, laid up, with fillers and / or binder tape, extruded PVC inner sheath, one layer of galvanizes round steel wire / strip armored and PVC outer sheath. Both inner and outer sheath shall be conforming to IS 1554 / 7098 (Part-I) 1988 (amended up to date) and bearing ISI mark in standard drum length complete with test certificates for type test, routine test and acceptance test as specified. | ||
5 | 3.5/4 C X 25 Sq.mm | 150 | Mtrs. |