- Home
- >
- Tender
- >
- Uttar Pradesh Tender
- >
- Department of LUCKNOW DEVELOPMENT AUTHORITY
- >
NTID 39806366
ProcXpert
Share Your purchase requirement, Our ProcXpert team will Connect you to right Supplier.
Inquiry Now
Hussainabad Chetra Sthith Musi, Lucknow - Tender Details
LUCKNOW DEVELOPMENT AUTHORITY
Lucknow, Uttar Pradesh, India
NTID 39806366
- Opening Date : Thu 10th April, 2025
- Closing Date : Wed 9th April, 2025
- ₹ 12779000.00
- NTID 39806366
Tender Description
Documents
Get Complete Tender Details Now – Download the Document!
Buy This Document-
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
-
721.3 kBOil_India_ExtraDoc...Oil_India_ExtraDocument-GCO0449P23.pdf
Costs
-
EMD
255600.00 -
Document Cost
4366.00 -
Estimated Cost
12779000.00
BOQ Items Total Items : 169 | Total Qty : 4269
# | Item | Quantity | Units |
---|---|---|---|
1 | H. T. SYSTEM | ||
2 | 11 KV Incoming System by SEB / Client | ||
3 | S.I.T.C. of 11 K V Vacuum Circuit Breaker panel indoor mounted, self-standing type (with 25KA fault level) conforming to IS: 2156 with degree of protection to IPH3 as per I S 3427. The VCB shall conform to I S 13118 and have a continuous current capacity of 630 Amps (25KA/1 sec) and shall be vertically isolated, horizontally draw-out type, three pole, trip free, complete with 24V D C trip-coil, Auxiliary contact for trip circuit, Spring Charging Motor, C T, P T, metering & protection as required. : Energy Meter with MDI suitable for 200/100/5A/350 MVA (1250 Amp) | 1 | No |
4 | S.I.T.C. 400 KVA, 11KV / 433V, 50Hz, 3 phase Delta / Star connected ONAN out-door type oil filled transformer with Dyn-11 vector group suitable for floor mounting. The transformer shall have Off Load Tap Changer in steps of 2.5 % from +10 % to -10% and shall conform to IS: 1180 / IS: 2026, 1977, Level II, (latest edition). Transformer shall be complete with: : Oil conservator, Oil cooling fins/tube radiaters fitted on either side of the oil tank containing the HT & LT windings. The windings shall be with copper layered for LT side and Cu foil for HT side with class A insulation. : Transformer - IS : 1180 (Part I) : 2014 : Oil - IS : 335 : 1993 : HT side of the transformer shall be suitable for cable termination with porcelain bushing conforming to I S: 2099, complete with cable end-box & cable disconnecting chamber and the LT side suitable for Cables termination with Epoxy bushing conforming to I S: 3347 as follows: (MR) | 1 | Nos |
5 | : H. T. Side : 1 x 3 C x 120 sq. mm. X LPE cable. |