Facebook
Description

Augmentation Of Sewage System Including Sewage Treatment Plant At Cme Pune

Tendering Authority: Military Engineer Services

India, Maharashtra, Pune

NTID

25106267

Last Date For Submission

01 Nov, 2022

Closing Date

01 Nov, 2022

BOQ Items
# Item Quantity Units
1 SCH 'A PART-I (BUILDING/STRUCTURAL WORKS) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
2 Construction of civil structures for Sewage Treatment Plant (STP based on MBBR technology : for Electro Mechanical Equipments refer Item Nos 1.1 to 1.114 here-in-after) of capacity 3 MLD comprising of following items/ structures all as shown on drawing No CEPZ/2021/KK/01 sheet No. 1/35 to 35/35 including related structural drawing complete all as shown on drawing and all as specified and directed.:- 1.00 Each Job
3 (a) Blower House and admin bldg
4 (b) Trolly room & Centrifuge house
5 (c) Sludge sump cum Pump house
6 (d) MBBR (Aeration) Tank
7 (e) Tube Settler
8 (f) Equalisation tank
9 (g) Anoaxic Tank
10 (h) Chlorine contact tank
11 (j) Sludge Drying Beds
12 (k) Primary units as shown on drawings (Stilling chamber, Manual Screen chamber & Grit chamber)
13 (l) Compound wall
14 (m) Raw water Sewage sump
15 (n) Treated water storage tank
16 (o) Filter Base
17 NOTE: Schedule A Part I to XIII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-13 only.
18 Total amount of Sch 'A' Part-II (Internal Electric Supply) 1.00 LUMP SUM
19 Total amount of Sch A Part III (Internal Water Supply) 1.00 LUMP SUM
20 Total amount of Sch A Part IV (External Electrification) 1.00 LUMP SUM
21 Total amount of Sch A Part V (Treated Water Supply) 1.00 LUMP SUM
22 Total amount of Sch A Part VI (Road /Path & Hard Standing) 1.00 LUMP SUM
23 Total amount of Sch 'A' Part-VII (Area drainage) 1.00 LUMP SUM
24 Total amount of Sch 'A' Part-VIII (Fencing and Gate) 1.00 LUMP SUM
25 Total amount of Sch A Part IX (Sewage Line) 1.00 LUMP SUM
26 Total amount of Sch A Part X (Pumping Main) 1.00 LUMP SUM
27 Total amount of Sch A Part XI (Pumping Machinery) 1.00 LUMP SUM
28 Total amount of Sch A Part XII (Excavation, Earthwork & Site Clearance) 1.00 LUMP SUM
29 Total amount of Sch A Part XIII (Demolition & Dismantling) 1.00 LUMP SUM
30 SCH 'A PART XV : (Miscellaneous B/R and E/M works including Electro Mechanical Equipments of Sewage Treatment Plant) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
31 Electro Mechanical Equipments of Sewage Treatment Plant:-
32 Supply , install , testing & commissioning Manual coarse screen 0.5m wide x 0.5m SWD(0.5 m SWD +0.3m FB), 20mm opening, Material of Construction(MOC) - SS304. The bar screen shall be located at a suitable elevation and each shall be designed to cater peak flow. The screen shall consist of 20 mm clear space in between. The screen shall be installed at an inclination of 45 deg to 60 deg to the horizontal complete all as specified and directed. 1.00 Each
33 Supply, install, testing & commissioning Cast Iron gates manually operated 0.5m x 0.5m at inlet & outlet of screens and inlet of grit chamber/by pass, to be placed in RCC channel, opening shall be at the bottom of gate, hand wheel lift mounting shall be to yoke, Material of construction (MOC) shall be as follows - Frame, yoke, slide, stem guide, stem extension - SS304L, Stem cover - clear polycarbonate, Side-seals - self adjusting UHMWPE, Bottom seal - resilient neoprene, Position indicator - Maylar slip, Stem configuration - Threaded rising stem, type 303MX stainless steel, Manual operation - By hand wheel complete all as specified and directed.(Gate for screen Inlet/Outlet) 2.00 Each
34 Supply & install, Testing & Commissioning Cast Iron gates manually operated 0.5m x 0.5m at inlet & outlet of screens and inlet of grit chamber/by pass, to be placed in RCC channel, opening shall be at the bottom of gate, hand wheel lift mounting shall be to yoke, Material of construction (MOC) shall be as follows - Frame, yoke, slide, stem guide, stem extension - SS304L, Stem cover - clear polycarbonate, Side-seals - self adjusting UHMWPE, Bottom seal - resilient neoprene, Position indicator - Maylar slip, Stem configuration - Threaded rising stem , type 303MX stainless steel, Manual operation - By hand wheel complete all as specified and directed. (Gate for grit chanber) 1.00 Each
35 Supply , install , Testing & commissioning Manual fine bar screen 0.5m wide x 0.5m SWD +0.3m FB, 10mm opening, Material of Construction(MOC) - SS304, The bar screen shall be located at a suitable elevation and each shall be designed to cater peak flow. The screen shall consist of 10 mm clear space in between. Suitable dimensions of the chamber shall be provided in order to maintain a velocity of 0.6m/s to 1.2m/s during the peak flow.The screen shall be installed at an inclination of 45 deg to 60 deg to the horizontal complete all as specified and directed. 1.00 Each
36 Supply install,Testing & commissioning MBBR technology including imported virgin plastic made PP/HDPE media with minimum specific surface area 250 sqm/cum, minimum volume in aeration tank shall be 30% along with SS304 sieves at the outlet to trap the media and PVC/SS coarse bubble airomega diffuser system suitably designed to have media always in suspension complete all as specified and directed. 1.00 Each
37 Supply, installation Testing & commissioning of standard lengths ISI mark rigid unplasticised 25mm PVC pipes suitable for air grid system and for other components with solvent cement joints including cost of couplers as per IS specifications no 4985/1988 including cost of jointing material i.e. solvent cement etc. (self fit type to be joined with cement joint) complete all as specified and directed. 20.00 RM
38 Supply, installation Testing & commissioning of standard lengths ISI mark rigid unplasticised 50mm PVC pipes suitable for air grid system and for other components with solvent cement joints including cost of couplers as per IS specifications no 4985/1988 including cost of jointing material i.e. solvent cement etc. (self fit type to be joined with cement joint) complete all as specified and directed. 60.00 RM
39 Supply, installation Testing & commissioning of standard lengths ISI mark rigid unplasticised 100mm PVC pipes suitable for air grid system and for other components with solvent cement joints including cost of couplers as per IS specifications no 4985/1988 including cost of jointing material i.e. solvent cement etc. (self fit type to be joined with cement joint) complete all as specified and directed. 56.00 RM
40 Supply, installation Testing & commissioning of standard lengths ISI mark rigid unplasticised 150mm PVC pipes suitable for air grid system and for other components with solvent cement joints including cost of couplers as per IS specifications no 4985/1988 including cost of jointing material i.e. solvent cement etc. (self fit type to be joined with cement joint) complete all as specified and directed. 64.00 RM
41 Supply install, testing & commissioning Air blowers with motors, accoustic enclosures with all accessories, Each Capacity 2600 Cum/hr with 0.45Kg/Sqcm, Single stage, air cooled, twin lobe type to supply air for aeration (EQT,MBBR tank, sludge sump etc.), Continuous duty, design code BS 1571, End connection flanged as per ANSI B 16.5 150lb, Noise level shall be less than 85 db at 1.86 m distance from blower, Motor shall be TEFC sq cage induction motor Class F, IP 55 protection, Material of Construction(MOC) - Casing CI IS 210 Gr FG 260, Shaft EN 24, Foundation bolts SS304, Accessories to be provided with each blower - Base frame, suction filter, silencer, safety relief valve, V-belt, drive & driven pulleys, belt guard, foundation bolts, pressure gauge with built-in snubber & glycerine filled, accoustic hood etc., complete all as specified and directed. 2.00 Each
42 Supply, delivery and erection at site MS chain electric hoist with trolley for air blower room, cap=3T, 6m lift alongwith TEFC sq cage induction motor IP-55 class F complete all as specified and directed. (For air blower) 1.00 Each
43 Supply, delivery and erection at site MS chain electric hoist with trolley for centrifuge platform, cap=3T, 6m lift alongwith TEFC sq cage induction motor IP-55 class F complete all as specified and directed. (For centrifuge) 1.00 Each
44 Supplying and fixing triple spur gear type chain pulley block suitable for capacity as 12m lift complete with load chain suitable for above lift,tested to 50% over load as per IS:3832 carrying IS mark complete all as specified and directed. (For sewage pump) 1.00 Each
45 Supply, install, testing & commissioning Polyelctrolyte dosing tank agitators slow speed SS304, with motors, continuous duty operation to mix DWPE solution 0.1% from HDPE tank of size 2000 liters solution viscosity 200 cp, sp. Gravity 1.05, impeller turbine type of 100 rpm speed, gear box shall have service factor of 2, sq cage induction motor IP 55 protection class F insulation, Material of Construction(MOC) shall be - impeller, shaft & coupling - SS304, complete all as specified and directed. 1.00 Each
46 Supply, install, testing & commissioning Polyelectrolyte dosing pump, mechanically actuated diaphragm type metering pump, Capacity 100 LPH, continuous duty, manual stroke adjustment, tolerance on capacity +/- 5%, flooded suction, discharge pressure 1.50 kg/cm2, fluid consistency 0.1 to 0.5%, viscosity 200 cp, Material of Construction(MOC) - Housing CI IS 210 GR. FG 260, Head PP, Antisyphon valve, hardwares, strainer, PRV - SS 304, Motor TEFC sq cage induction type, IP 55, Class F insulation complete all as specified and directed. 2.00 Each
47 Supply, install, testing & commissioning of Overhead tank HDPE 3000 litres capacity, covered on top, provided with conductivity type level controller coupled with ON/OFF arrangement of submersible water pump, with necessary GI piping for inlet, outlet, overflow, drain and gun metal gate valves 25 NB at each location complete all as specified and directed. 1.00 Each
48 Supply, install, testing and commissioning of UPVC ring tight pipes conforming to IS 4985:2000, perfect linking at joints, and cuts of pipes wherever necessary including jointing of UPVC pipes and including specials with jointing of approved type and giving hydraulic testing to the required pressure as per ISS of 15NB - 10 kg/cm2 complete all as specified and directed. 40.00 RM
49 Supply, instll,testing & commissioning Hypochloride dosing overhead tank 1000 Litres capacity HDPE, including all UPC accessories, with and including MS angles support, painting with anti corrosive paints, dosers complete as per manufacturer instructions and all as specified and directed by the Engineer in charge. 1.00 Each
50 Supply & Fixing Hypochloride dosing pump, mechanically actuated diaphragm type metering pump, Capacity = 50 LPH, continuous duty, manual stroke adjustment, tolerance on capacity +/- 5%, flooded suction, discharge pressure 1.50 kg/cm2, fluid consistency 0.1 to 0.5%, viscosity 200 cp, Material of Construction(MOC) - PP, Antisyphon valve, hardwares, strainer, PRV - SS 304, Motor TEFC sq cage induction type, IP 55, Class F insulation complete all as specified and directed. 2.00 Each
51 Supply, install, testing & commissioning of service water pumps with motors 5 M3/Hr @ 25 MWC, CI submersible type motor IP 55 with quick action coupling including NRV at the delivery complete all as specified and directed. 1.00 Each
52 Supply, fixing, installation, testing and commissioning of filtration system comprised of 2 nos pressure sand filters each of vessel size 2.4m dia x 1.5m HOS ( Average flow 136M3 /Hr for 22 hrs). . . Design parameters: Surface loading rate 2 nos activated carbon filters each of 2.6m dia x 1.5m HOS ( Average flow 136M3 /Hr for 22 hrs), Material of pressure vessel MSEP, minimum thickness of plate shall be 6mm with and including all necessary frontal piping and valves, back washing system complete all as specified and directed. 1.00 Each Set
53 Supply & Fixing PP ball valves 15NB screwed conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc all as specified and directed. 9.00 Each
54 Supply & Fixing CI wafer type butterfly/gate valves PN 1.6 BS 5155, manual 50NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed. 5.00 Each
55 Supply & Fixing CI wafer type butterfly valves PN 1.6 BS5155, manual 150NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed. 3.00 Each
56 Supply & Fixing CI dual plate type check valves PN 1.6 BS 5155, 15NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed. 4.00 Each
57 Supply & Fixing CI dual plate type check valves PN 1.6 BS 5155, manual 50NB conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc. all as specified and directed. 2.00 Each
58 Supply & Fixing CI sluice valve PN 1.6 BS 5155, manual 80NB Tube settler conforming to relevant ISS with latest amendments complete with all led, lift and fixing including cost of nuts and bolts etc.all as specified and directed. 4.00 Each
59 Supply and Fixing glycerene filled Stainless steel pressure gauge of 150mm dia suitable for the pumpsets with and including nipple, stop cock & two way cock for cleaning & necessary length of copper tubing complete all as specified and directed. 8.00 Each
60 Supply install, Testing & commissioning alum dosing pump, mechanically actuated diaphragm type metering pump, Capacity = 175 LPH, continuous duty, manual stroke adjustment, tolerance on capacity +/- 5%, flooded suction, discharge pressure 1.50 kg/cm2, fluid consistency 0.1 to 0.5%, viscosity 200 cp, Material of Construction(MOC) - Housing CI, IS 210 GR. FG 260, Head PP, Antisyphon valve, hardwares, strainer, PRV - SS 304, Motor TEFC sq cage induction type, IP 55, Class F insulation complete all as specified and directed. 2.00 Each
61 Supply, install, testing & commissioning centrifuge feed screw pumps with motors, Cap = 10.0 m3/hr @ 8 m head, to transfer biological sludge, continuous duty, single stage, helical screw rotor, with coupling guard, mechanical seal, foundation bolts, sp gr 1.05, viscosity 10 cp, sludge consistency 0.8-1.2%, max size of particle 60mm, Motor type TEFC, Class F insulation, IP 55 protection, Material of Construction(MOC) - Casing, rotor, pump shaft - alloy steel, casing ring - nitrile bonded, foundation bolts - SS304, base plate - MSEP, pump speed shall be less than 400 rpm. complete all as specified and directed. 2.00 Each
62 Supply, install, testing & commissioning for Centrifuge SS316 solid bowl type, Cap = 10 m3/hr, liquid handled - biological sludge, solid consistency 0.8 - 1.2%, sp gr of sludge 1.05, no. of operating hrs 16, vibration level controlled to 50 micron using anti-vibration pads, centrally lubricated, overload protection using torque switch, Motor TEFC sq cage IP 55 protection class F insulation, RPM shall be less than 1500, Material of Construction(MOC) - Casing C.S., Bowl, screw, foundation bolts SS304, Base frame MSEP complete all as specified and directed. 1.00 Each
63 Supply, install, testing & commissioning Tube settler media support structure shape and size as per manufacturer recommendations complete all as specified and directed. 1.00 Each Set
64 Supply, install, testing & commissioning Tube settler media in PVC modules of size 2.5mX0.3m X0.5m to cover all surface area of tank, providing 75 corbels in RCC walls on both sides at 1.6 m below FSL to support tube modules. Tube modules to be fabricated by fixing rigid PVC square tubes 50mmx50mm and 60 cm in length at 60 degree angle in opposite directions by solvent cement complete all as specified and directed. 1.00 Lot
65 Supply & Fixing alum dosing tank agitators slow speed SS304, with motors, continuous duty operation to mix alum solution 1% from HDPE tank of size 2000 Liters, solution viscosity 200 cp, sp. Gravity 1.05, impeller turbine type of 100 rpm speed, gear box shall have service factor of 2, sq cage induction motor IP 55 protection class F insulation, Material of Construction(MOC) shall be - impeller, shaft & coupling - SS304 complete all as specified and directed. 1.00 Each
66 Supply & fixing Wheel Barrows made in MS Construction, the body shall be either cut or folded from a single sheet of steel, the joints being secured by riveting or welding, or it may be solid-drawn pressing from single sheet. The design of Chassis and dimensions of the frame shall be such that the distance between the centre of the axle and the nearest point of the body does not exceed 23 cm, and the distance from the centre of the axle to the end of the handles is not less than 120 cm and not greater than 135 cm. The wheel shall be constructed of mild steel or cast iron and shall be of disk type or any other suitable design to ensure adequate strength. It shall be fitted with metal rim, or solid or cushioned rubber tyre. The axle or spindle shall be not less than 25 mm in diameter and the bearing length shall be not less than 25 mm at each end. (Size 0.5x0.4m) complete all as specified and directed. 2.00 Each
67 S & F, radial launder constructed from SS plate (SS-304) in tube settler of size 150mmx150mm and 5 mm thick providing notches at every 150 mm complete all as specified and directed. 40.00 RM
68 Supply, install , Testing & commissioning and giving test and trial of Submersible pump set with discharge capacity 125 m3/Hour, Head 15m at 2900 RPM speed and suitable for single as well as parallel operation with other pumps. Generally the pump shall conform to IS 9137, IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 2900 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. ( For Equilisation tank) 2.00 Each
69 Supply, install , Testing & commissioning of Electro Magnetic Flow meter (EMF) as per ISO 4064 with accuracy +/- 0.5% of measured valve and protection as per given specification. Flow meter shall be suitable for 125 m3/Hour 150 NB dia PTFE lined with 4020 mA out put without communication port remote cable length upto 5m, electrode material SS 316 L make including the pipe line cutting, levelling and installation of flow meter with necessary fixing arrangements complete all as specified and directed. 1.00 Each
70 Supply, fix and testing of Polyethylene pipes (Drain pipes from each sludge) drying beds to collecting sumps by gravity and pumping main from collecting sumps to sump conforming to IS 4984/14151/12786/13488 with necessary jointing materials and fittings like mechanical connection i.e. thread/insert joint quick release coupler joint/compression fitting joint or flanged joint complete all as specified and directed. 150.00 RM
71 Supply, fix and testing of HDPE equal tee of size 110x110x100 mm, PE 100, 110 mm, 6Kg/cm2 complete all as specified and directed. 6.00 Each
72 Supply, install, testing & commissioning of motor (Flash mixer) of suitable capacity to operate the peak flow condition with reduction gear motor shall be TEFC sq cage induction type, Class F insulation, MOC casing CI, IS 210 GR, FG 260, shaft EN-24 foundation bolts SS-304, with electrical equipments and hood for motor complete all as per manufacturer recommendations and as directed. Flash mixer M.O.C of shaft & impeller: SS 316 . Type of Impeller : Prepeller type . RPM of blade : 80 to 120 . Nos of blade: 2 . Length of blade : 0.3m . Width of blade : 0.075m . 1.00 Each
73 Supply, install , testing & commissioning of Mixers in Anoxic tank as required considering volume of tank with all accessories such as brackets, rods stand, lifting arrangement with electrical, mechanical items required, designed to operate for total volume, with blades and motors, mixer of 2 HP/1.5KW 960 RPM 415 V (+/-)10 %, combined variation (+/-) 10 %, cable size 1x7x1.5 and required cable length, propeller impeller type, MOC- Casing CI IS 210 Gr FG 260 etc and the parts shall be of SS complete all as per manufacturer recommendations and as directed. . Flash mixer M.O.C of shaft & impeller: SS 316 . Type of Impeller : Prepeller type . RPM of blade : 80 to 120 . Nos of blade: 2 . Length of blade : 0.3m . Width of blade : 0.075m . 2.00 Each
74 Supply, install , testing & commissioning of Pump and motor of flow of 0.0372M3/Sec head 20Mm, semi open type impeller, voltage 415 V (+/-) 10%, sphere passing size 100 mm, frequency 50 Hz (+/-) 3%, cable of required size and length, motor class F, IP-55 protection, MOC casing CI, IS 210 GR, FG 260, shaft EN-24 with required length of MDPE pipe from MBBR tank to anoxic tank with suitable valves as required, foundation bolts SS-304, with electrical equipments and hood for motor etc complete all as per manufacturer recommendations and as directed. ( For Re-circulation) 2.00 Each
75 Supplying and fixing, erecting at site MS chain pulley block with trolley for coarse screening chamber, of capacity 1Ton, 6m lift along with TEFC Sq cage induction motor IP55 class all as specified and directed. 1.00 Each
76 Supply, install, testing and commissioning of booster pump , multisate , horizontal, centrifugal , self priming, monoblock, pumps induction motor, 1450RPM, 50Hz, AC IP-54 protection, class G insulated hydraulically and dynamically balanced to give vibration eleminator pads complete all as specified and directed with following parameters:- . (A) Pump shall have inbuilt hair and lint stainer & protection against dry run, over load. . (B) Pump shall have flow rate of 70M3 /hr : . (C) Head 30 M . 3.00 Each
77 Supply, install, test & commissioning complete for Online Parameter Monitoring system for waste water treatment plant comprising the following:- 1.00 Each set
78 BOD/TSS/COD/pH- Muli-parameter analyser with sampling pump
79 Method- UV-VIS absorption dual beam spectrophotometry at 190-750 mm.
80 Calibration- Online auto zero calibration for COD/BOD/TSS with OFF SET correction, Manual SPAN calibration for COD/BOD/TSS/pH (in-place),
81 Operation cycle- continuous or batch type operating cycle,
82 Cleaning- automatic built-in cleaning function, user programmable cleaning,
83 Operation- Regent and chemical free analysis
84 Compensation- Auto turbidity and colour compensation,
85 Interface- Independent of flow and pressure variations,
86 Type- Advanced microprocessor based system,
87 Accuracy- COD/BOD/TSS: +5%-10% of F.S., pH: +0.1 pH,
88 Display type- Touch screen, alpha numeric display 240 x 128 pixels LCD with backlit
89 Response time- within 10 seconds
90 Measuring cycle- programmable/normally 3-5 minutes
91 Analog output- 0/4-20 mA,DC,isolated,
92 Enclosure protection -comply to IP 54,
93 Relay outputs- dry contact alarms for high and high-high set points, monitor failure, microprocessor, failure,
94 Power supply- 110-230 V AC, 50 Hz, 30 VA,
95 Digital output- RS 232/RS 485,
96 Ambient temperature- 0 to 50 Deg. C.
97 PC Configuration- CPU, Intel 13, HDD 500 GB SATA, RAM 4 GB, DDR 3 RAM, Ports: USB Standard, 1 LAN Monitor, TFT LED- 18.5 " (Colour)-DOS
98 Utility Software for SPCB & CPCB connectivity- Data connectivity of 1 multi-parameter analyser & 1 flow meter, CPCB server connectivity, Data logging, trending & viewing, For 4 tags, RS 485 to USB converter at PC end (01 No)
99 Make- Forfbes Marshal/Tethys
100 Supply, install, test & commissioning complete for Chlorine Analyzer for Online Monitoring comprisng the following- 1.00 Each set
101 Resolution- 0.01 mg/l,
102 Accuracy= 2% of Full scale,
103 Response time- 90 to 60 seconds,
104 OperatingTemperature - 5 to +70 Deg C,
105 Sensor Measuring Electrode type- Amerometric type 9potentiometric free chlorine sensor)
106 Sensor electrode material_ Shaft: Glass, Electrode: Gold, Reference electrode: Ag/Tepox gel,
107 Diaphragm: Ceramics, Gasket: EPDM,
108 Sensor automatic cleaning- ASR -Automatic sensor cleaning system,
109 Transmeter type- Microprocessor based programmable,
110 Display- backlit LCD graphic 128 x 64 pixcels,
111 Analogue output- 3 x 4 to 20 mA, max. 400 ohm all galvanically isolated, Enclosure moc & protection class- Die cast aluminium & IP66/NEMA4X
112 Make-Forfbes Marshal/Tethys
113 Material & labour for Auto desludge valve, electric actuator, timer based type (01 No at bottom of Clari-Tuber settler). 1.00 Each
114 Material & labour for Air rotameter, glass tube type. 4.00 Each
115 (Pumping Machinery)
116 Providing, installing, commissioning and giving test and trial of Submersible non-clog sewage pump set for capacity of Discharge 70m3/hr, Head - 17.25 m with and including suitable size star delta starter of appropriate rating/capacity to handle unscreened crude sewage specific gravity 1.05 and solids and organic waste upto 100 mm size. The pump should be capable of delivering a discharge (stated below) against head (stated below) at 1450 RPM speed and suitable for single as well as parallel operation with other pumps. Generally the pump shall conform to IS 9137, IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 1450 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. 2.00 Each
117 Providing, installing, commissioning and giving test and trial of Submersible non-clog sewage pump set for capacity of Discharge 126m3/hr , Head - 17.25 m with and including suitable size star delta starter of appropriate rating/capacity to handle unscreened crude sewage specific gravity 1.05 and solids and organic waste upto 100 mm size. The pump should be capable of delivering a discharge (stated below) against head (stated below) at 1450 RPM speed and suitable for single as well as parallel operation with other pumps. Generally the pump shall conform to IS 9137, IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 1450 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. 1.00 Each
118 Providing, installing, commissioning and giving test and trial of Submersible non-clog sewage pump set for capacity of Discharge 248.40m3/hr , Head - 17.25 m to handle unscreened crude sewage specific gravity 1.05 and solids and organic waste upto 100 mm size. The pump should be capable of delivering a discharge (stated below) against head (stated below) at 1450 RPM speed and suitable for single as well as parallel operation with other pumps. Generally the pump shall conform to IS 9137,IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 1450 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. 1.00 Each
119 Providing, installing, commissioning and giving test and trial of Submersible non-clog sewage pump set for capacity of Discharge 374.40m3/hr , Head - 17.25 m with and including suitable size star delta starter of appropriate rating/capacity to handle unscreened crude sewage specific gravity 1.05 and solids and organic waste upto 100 mm size. The pump should be capable of delivering a discharge (stated below) against head (stated below) at 1450 RPM speed and suitable for single as well as parallel operation with other pumps. Generally the pump shall conform to IS 9137, IS 5600 with Squirrel cage, induction electric motor A.C. 3 phase, 415 V, 50 Hz, Voltage/frequency variation +/-6% and 3% respectively and 1450 RPM speed motor rating to have a margin of 15% over the maximum power absorbed by any of the pumps during the entire working range of pump. Electric motor shall generally conform to IS : 325 complete all as specified and directed. 1.00 Each
120 Supply & Fixing double flanged sluice valve 150 mm dia confiming for IS 2906/14846 including warm gear arrangement as per test pressure stainless steel spindle caps including all taxes transportation etc complete all as specified and directed. 3.00 Each
121 Supply & Fixing double flanged sluice valve 200 mm dia confiming for IS 2906/14846 including warm gear arrangement as per test pressure stainless steel spindle caps including all taxes transportation etc complete all as specified and directed. 1.00 Each
122 Supply & Fixing double flanged sluice valve 250 mm dia confiming for IS 2906/14846 including warm gear arrangement as per test pressure stainless steel spindle caps including all taxes transportation etc complete. 1.00 Each
123 Supply and Fixing double flanged refluxe valve 150mm dia with brass spindle confiming for IS 5312 part I (1984) including all taxes (centra and local), railway freight, inspection charges, unloading from railway wagon,loading into truck transportation upto department stores/site/unloading stacking etc.complete. 3.00 Each
124 Supply and Fixing double flanged refluxe valve 200mm dia with brass spindle confiming for IS 5312 part I (1984) including all taxes (centra and local), railway freight, inspection charges, unloading from railway wagon, loading into truck transportation upto department stores/site/unloading stacking etc.complete. 1.00 Each
125 Supply and Fixing double flanged refluxe valve 250mm dia with brass spindle confiming for IS 5312 part I (1984) including all taxes (centra and local), railway freight, inspection charges, unloading from railway wagon,loading into truck transportation upto department stores/site/,unloading stacking etc.complete. 1.00 Each
126 Supply & Fixing jointing 80 mm dia, PN 1, Air Valve as per IS -108045 and standard specifications double orifice type combined with screw down isolating valve,small orifice elastic ball resting on a gun metal orifice nipple,large orifice vulcanite ball seating on moulded seat ring,inlet face and drilled, loading unloading, tranportation upto departmental stores/site, etc. complete all as specified and directed. 3.00 Each
127 Supplying and erecting 40 kVAR, 440 V Three phase, 50 cycles, THYRISTER SWITCHED MICRO APFC PASSIVE FILTER PANEL, consisting of 6 steps 10 KVAR x 2 + 5 KVAR x 4) of APP type capacitor units confirming to IS- 13585 ( Part I ) 1994 with harmonic filter reactors, as per specification complete with all accessoriescomplete all as specified and directed. 1.00 Each
128 Providing, erecting Pressure gauge of 0 to 30 Kg/cm2 range complete with syphone tube,isolating cock suitable for 12 mm dia G.I. Pipe.Pressure gauge shall be installed as directed ,with tapping on rising main (100mm Dia) complete all as specified and directed. 3.00 Each
129 Design, fabricate, supply & install Mechanical level indicator float and chord type for the pump house complete all as specified and directed. 1.00 Set
130 Providing and fixing in position copper lightening conductor including copper rod of 20 mm dia as per upper terminal 1.5 m long with a knob at end and with conical spike at top,copper tape conductor 20x3 mm size, copper earth plate of size 3 mm thick x 0.81 sqm in aera clamps at 1 m centre to centre including necessary excavation, laying and fixing the conductor, providing and fixing the conductor, providing and fixing 40mm GI pipe upto 3 M height from ground and 0.5 M below ground including making all connections, filling earthing pit with charcoal, salt, etc and refilling and watering etc. complete as per specifications laid down in relevant I.S.codes, for tape of 10 m length complete all as specified and directed. 2.00 Each
131 Supply, laying and fixing to wall, laid in trenches, passing through pipes electric cable 1100 v grade sranded copper conductor, 10 Sqmm 3 core PVC insulated & PVC sheathed, unarmoured, flat submersible type complete with necessary connectionscomplete all as specified and directed. 120.00 RM
132 Supply, laying and fixing to wall, laying in trenches, passing through pipes electric cable 100 v grade sranded copper conductor, 3 core PVC insulated & PVC sheathed unarmoured, flat submersible type complete with necessary connections but 1.5 sq.mm, 9 core to be laid for controls & signals of submersible pump. 120.00 RM
133 Supply, laying and fixing to wall, laying in trenches, passing through pipes connecting up XLPE insulated armoured,heavy duty electric cable with 100 V grade, 3.5 Core, 50 sqmm Aluminium conductor PVC armoured cable complete all as specified and directed. 120.00 RM
134 Providing & laying and terminating 4 Core, 16 sqmm Copper conductor PVC armoured cable, 100 V grade for various pumps and Blowers in the plant complete all as specified and directed. 300.00 RM
135 Supply, laying and fixing to wall, laying in trenches, passing through pipes connecting up XLPE insulated armoured,heavy duty electric cable with 100 V grade, 3.5 Core, 185 sqmm Aluminium conductor PVC armoured cable for Incoming to Panel from Transformer and DG set complete all as specified and directed. 200.00 RM
136 Supply, laying and fixing to wall, laying in trenches, passing through pipes connecting up XLPE insulated armoured,heavy duty electric cable with 100 V grade, 3.5 Core, 150 sqmm Aluminium conductor PVC armoured cable for Incoming to Panel from Transformer and DG set complete all as specified and directed. 100.00 RM
137 Supply & Install HT 22 KV outdoor type gang operated air break switch triple pole, 3 insulator double stalk type suitable for horizontal or verticle mounting with complete accessories such as mounting channels, bolts & nuts, washers, GI operating rod of suitable length etc. of rating up to 200 Amps including locking arrangements including Godrej 7 lever lock NAVATAL with 3 keys complete all as specified and directed. 1.00 Each
138 Supply and fix dropout fuse unit expulsion type outdoor type 200 A rating single pole mounted on 2 insulators fixed to and including MS channel with nuts, bolts washers etc. synthetic bounded fuse carrying tube complete with HT fuse element 25A capacity for HT 22 KV working pressure complete all as specified and directed. 1.00 Set of three
139 Supply and fixing lightening arrestor non linear type with mounting accessories complete fixed on cross arms of pole and connected with aluminium conductor with all fittings transmission class earth system, having discharge capacity of 10 KA and suitable for working pressure of 22 KV grade complete all as specified and directed. 1.00 Set of three
140 M & L for HT 22 KV insulator pin type, dia 160mm and height 200mm, polymer type including one galvanized MS spindle, 2 GI washers, one GI nut of standard size complete all fittings and fixturescomplete all as specified and directed. 6.00 Each
141 M & L for HT 22 KV insulator disc type, dia 255mm, height 145mm, porcelain, vitreous, white, brown, or green insulater or polymer type including CI stud, GI bolt nuts, washers, clamps, etc. suitable for fixng on cross arms complete all as specified and directed. 6.00 Each
142 S & F of 4mm dia GS wire 50x50 mm mesh, made up into mattresses or cages, lapped, wired and laid in position, including fixing up with suitable nuts, bolts, washers etc and reinforced with suitable MS flat iron complete all as specified and directed. .Note: Cost of MS flat iron and angle iron supports will be measured and paid seperately. 70.00 Sqm
143 Supplying, installing, testing and commissioning of AC 3 phase 50 HZ 200 KVA capacity energy efficient level-III transformer step down, plinth mounted outdoor type 22000/433 volts (at no load), all as per IS-1180 Part-I, copper wound, oil immersed, naturally cooled with external cooling tubes, core type, delta connected on primary (HV) side and star connected on secondary (LV) side in accordance with vector symbol DYN-11 (vector group-4) with neutral brought on secondary (LV) side & having tappings in equal steps of 2.5 % from (+) 5% to (-) 7.5% on primary side by means of hand operated off load tap changing gear, so as to change/correct L.T voltage on secondary side including provision of all necessary / standard fittings and mainly comprising of :- 1.00 Each
144 (a) One cable box on primary H.V side having cable glands suitable for 185Sqmm 3 core XLPE 22 KV H.T cable (consisting of 3 Nos porcelain H.T bushings with brass/ gun metal bushing rods complete with nuts and washers)
145 (b) One cable box on secondary (LV) side consisting of 4 Nos porcelain bushings with GM bushing rods complete with GM nuts, and washers with one No cable gland suitable for reception of outgoing L.T. PVC sheathed armoured cables of size 2 x 120 sqmm 3.5 core .
146 (c) Oil conservator with filter type, drain valve and oil level gauge.
147 (d) Dehydrating breather with first fill of denydrating agent .
148 (e) Explosive vents.
149 (f) Thermometer pocket on tank cover.
150 (g) One No 100 mm dia dial type thermometer vapour pressure type having range 0-120 degree centigrade with temp reading pointer, max temp indicator and resetting device
151 (h) Rating plate with terninal markings.
152 (j) Two earthing terminals on tank/tank cover to facilitate fixing of 32 x 6 m GI earth strip.
153 (k) Oil level gauge.
154 (l) Oil drain and filter vlalves.
155 (m) Oil filler hole with cap/plug with connections complete.
156 (n) Lifting lugs.
157 (o) Air relief valve plug.
158 (p) Four plan solid cast steel detachable rollers.
159 (q) First fill of fresh oil conforming to relvant IS and tested upto 40 KV dielectric strength.
160 (r) Extra bushing for neutral outside the L.T cable box for providing independent earthing for neutral.
161 (s) Provision of 2 Nos danger boards 250 x 200 mm size made out of 1.6 mm thick M.S. plate, vitreous enameled white, with letters. figures of voltage and conventional skull and bones in signal red colour , one at H.T side and other on L.T side.
162 (t) Any other fittings / accessories so as to conform the whole transformer to IS-2026.
163 Supplying Installing testing & commissioning diesel engine driven generating set 415 V, 3 Phase, 4 Wire as per BS 5514/IS-10002 complete with Automatic on mains failure (AMF) panel, of capacity continuous rating 200 KVA at NTP conditions with acoustic enclosure considering all derating factors and comprising of the following :- 1.00 Each
164 (a) ALTERNATOR : Closed type regulated with brushless self excitation 415 V, 3 Phase, 4 Wire, 50 HZ, 0.8 PF 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load Anti vibration mounted drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft, with necessary controls as recommended by the manufacturer confirming to BS-5000/IS-4772 capable of supplying unbalanced load, alternator make : Stamfort/Crompton/Jyoti Electric Co/Cummins
165 (b) Engine : Multi/cylinder compression ignited, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump hydraulic governing mechanism, all as per BS-5514/IS-3046, 1500 RPM class A1 governing/ control gauges. RPM /Hours meters etc suitable for generating application and capable of giving an output of 200 KVA for coupled altemator under NTP conditions, complete with following :-
166 (i) Flywheel with housing ad mesh protection.
167 (ii) Flexible coupling set dirctly mounted to engine and alternator with coupling guard
168 (iii) Air-cleaner dry type with vacuum indicator.
169 (iv) Fuel pump FIP/CRDI and fuel piping 15mm MS Pipe with bends, flanges etc
170 (v) Fuel filter with water separator and filter element.
171 (vi) Lub-oil filter with filter element
172 (vii) DC heavy duty starter 24 Volts
173 (viii) Storage batteries 180 AH 24 Volts
174 (ix) Engine overspeed stop/trip switch
175 (x) Radiator with fan, thermostat
176 (xi) Dynamo/Alternator for battery charging
177 (xii) Corrosion inhibitor coolant.
178 (xiii) Engine control panel electronic digital display type consisting of battery voltage indicator lub oil temp and pressure gauges, coolant water temp gauge RPM indicator cum hour meter etc
179 (xiv) Safety controls for alram due to high water temp (HWT) and low luib oil pressure (LLOP)
180 (xv) Any other devices/ accessorsdies recommended/ supplied by the manufacturers as standard eqpt. Engine Make : Cummins/Greaves/Perking
181 (c) The engine and alternator will be coupled, aligned and mounted on a sp-acially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads, Make Dunlop/ Polybond of reqd size and numbers as recommended by the manufactureres for mounting of 200 KVA DG Set
182 (d) Indoor Automated mains failure panel fabricated from CRCA Sheet, self supporting of size not less than 1.2x1x0.3m suitable for unmanned operation of DG set incl necessary contactors and Bi- passing arrangements, manually operated change over 400Amps with all type of indicators and remote controlled operation of DG set and incl necessary wiring between DG set and AMF panel inside GI pipe 40 mm dia as specified and directed.
183 (e) Diesel tank of adequate capacity for 24 hrs continous run on full load, with caliberated scale (fuel level indicator ) dip stick, fuel inlet/outlet, Air vent drain plug and intlet arragement for direct filling, incl suitabsle size gate valve in outlet, tank to be fitted at suitable height.
184 (f) Acoustic encloser with canopy cover to be provided
185 (g) PCC/RCC foundation complete as per manufacturers design.
186 (h) Documents : Three sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catelogue, warranty/test certificates, schematic diagrams of control pannels.
187 (j) Misc items : List of tools and two years normal maintenance spares as per manufactures recommended lists, duly prices item wise
188 ( k) Change over switch 400 Amps 415 volts, 4 pole -01 No
189 Note:- (i) Contractor will satisfactorily conduct load test sof DG Set for 12 hrs incl run on 10% overload for 1 hr
190 (ii) Testing eqpt will be arranged by the contractor.
191 (iii) Fuel required for 1st load test shall be suppled by the department free of cost.
192 (iv) All connections from AMF to DG set and DG set to Existing panel for power and control cables are to be connected by the contractor.
193 Supply, installing, testing and commissioning, weather, dust and vermin proof Feeder Piller box factory made, outdoor type of suitable size so as to accommodate the following accesoris, depth not less than 500mm, IP 54 and all as per IE rules, prewired and fabricated with 3.15mm thick CRCA sheet exoxy power coated double door with aprons, duly powder coated mounted on MS angle iron frame 50x50x6mm welded in shape with two coats of synthetic enamel paint over a coat of red oxide primer including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded coarse stone aggregates complete with leg 50cm grounted in ground in PCC at 40cm above ground including connection cable with cable glands, lugs etc and consisting of the following :- Note : PCC plinth will be measured and paid separately. 1.00 Each
194 (Main feeder pillar box)
195 (a) Copper bus bar 600 Amp(04 Nos)- 03 Nos for phase and 01 Nos for neutral duly colour sleeved mounted on epoxy insulator - 01 Set
196 (b) Incoming - MCCB 400 Amps, FP, 415V, 50Hz ICU 35 KA thermally adjustable between 70-100% - 01 No
197 (c) Outgoing
198 (i) MCCB 300 Amps, FP, 415V, 50Hz, ICU 25 KA thermally adjustable between 70-100% - 01 Nos
199 (ii) MCCB 200 Amps, FP, 415V, 50Hz, ICU 25 KA thermally adjustable between 70-100% - 01 Nos
200 (iii) MCB SPN 40 Amp, 10 KA series - 01 No
201 (iv) Digital LED Ammeter 3 phase, 0 to 600 Amps, Class 1.0 with suitable CTs & selector switch - 01 No
202 (v) Digital LED Voltmeter 3 phase, o to 600 Amps with selector switch class 1.0 - 01 No
203 (vi) RYB indicator lamp- Set of 3
204 Note : Panel shall be manufactured by the reputed manufacturer who is possession of type test certificate by CPRI not older than ten years.
205 Supply, installing, testing and commissioning, weather, dust and vermin proof LT distributin panel (Blower room) factory made, indoor type of suitable size so as to accommodate the following accesoris, depth not less than 500mm, IP 54 and all as per IE rules, prewired and fabricated with 2.00mm thick CRCA sheet exoxy power coated double door with aprons, duly powder coated mounted on MS angle iron frame 50x50x6mm welded in shape with two coats of synthetic enamel paint over a coat of red oxide primer including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded coarse stone aggregates complete with leg 50cm grounted in ground in PCC at 40cm above ground including connection cable with cable glands, lugs etc and consisting of the following :- Note : PCC plinth will be measured and paid separately. 1.00 Each
206 (a) Copper strip bus bar 400 Amp(04 Nos)- 03 Nos for phase and 01 Nos for neutral duly colour sleeved mounted on epoxy insulator - 01 Set
207 (b) Incoming - MCCB 300 Amps, FP, 415V, 50Hz ICU 25 KA thermally adjustable between 70-100% - 01 No
208 (c) Outgoing
209 (i) MCCB 160 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 02 Nos
210 (ii) MCCB 100 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 01 Nos
211 (iii) MCCB 63 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 03 Nos
212 (iv) MCCB 40 Amps, FP, 415V, 50Hz, ICU 16 KA thermally adjustable between 70-100% - 09 Nos
213 (v) MCB TPN 30 Amp, 10 KA series - 06 Nos
214 (vi) MCB SPN 40 Amp, 10 KA series - 04 Nos
215 (vii) MCB SPN 6 Amp, 10 KA series - 08 Nos
216 (viii) Star Delta starter for 3 ph blower motor 90 HP (for blower) with single phase preventor= 02 Nos.
217 (ix) Star Delta starter for 3 ph motor pump 40 HP with single phase preventor= 01 Nos.
218 (x) Star Delta starter for 3 ph motor pump 30 HP with single phase preventor= 01 Nos.
219 (xi) Star Delta starter for 3 ph motor pump 20 HP with single phase preventor = 02 Nos.
220 (xii) Star Delta starter for 3 ph motor pump 15 HP with single phase preventor = 06 Nos.
221 (xiii) DOL starter for 3 ph motor pump 10 HP with single phase preventor= 03 Nos.
222 (xiv) DOL starter for 3 ph motor pump 7.5 HP with single phase preventor = 02 Nos.
223 (xv) DOL starter for 3 ph motor pump 5 HP with single phase preventor= 04 Nos.
224 (xvi) Digital LED Ammeter 3 phase, 0 to 400 Amps, Class 1.0 with suitable CTs & selector switch - 01 No
225 (xvii) Digital LED Voltmeter 3 phase, 0 to 500 Amps with selector switch class 1.0 - 01 No
226 (xviii) RYB indicator lamp- Set of 3
227 Note : Panel shall be manufactured by the reputed manufacturer who is possession of type test certificate by CPRI not older than ten years.
228 (Pumping Machinery: Lifting Well)
229 Supply and laying of Terelex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia 63mm and inner dia 50mm polyethylene including coupler and bend with smooth internal and prolified external surface for non pressure under ground cable complete all as specified and as directed. 780.00 RM
230 Supply and laying of Terelex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia 110mm and inner dia 95mm polyethylene including coupler and bend with smooth internal and prolified external surface for non pressure under ground cable complete all as specified and as directed. 229.00 RM
231 Supply, laying, jointing, testing and commissioning of 120 Sqmm, 3.5core LT cable 1100V grade, XLPE insulated armoured and PVC sheathed with stranded aluminium conductor heavy duty ,conforming to I 1554 Part 1/ISI marked to be laid in trenches fixed along the poles or through GI pipe laid under floors, road etc fixed concealed in walls encased in GI pipe etc complete all as specified and as directed. 200.00 RM
232 Supply, laying, jointing, testing and commissioning of 50 Sqmm, 3.5 core LT cable 1100V grade, XLPE insulated armoured and PVC sheathed with stranded aluminium conductor heavy duty, conforming to I 1554 Part 1/ISI marked to be laid in trenches fixed along the poles or through GI pipe laid under floors, road etc fixed concealed in walls encased in GI pipe etc complete all as specified and as directed. 50.00 RM
233 Supply, laying, jointing, testing and commissioning of 25 Sqmm, 3.5 core LT cable 1100V grade, XLPE insulated armoured and PVC sheathed with stranded aluminium conductor heavy duty, conforming to I 1554 Part 1/ISI marked to be laid in trenches fixed along the poles or through GI pipe laid under floors, road etc fixed concealed in walls encased in GI pipe etc complete all as specified and as directed. 550.00 RM
234 Supply, laying, jointing, testing and commissioning of 10 Sqmm, 2 core LT cable 1100V grade, XLPE insulated armoured and PVC sheathed with stranded aluminium conductor heavy duty ,conforming to I 1554 Part 1/ISI marked to be laid in trenches fixed along the poles or through GI pipe laid under floors, road etc fixed concealed in walls encased in GI pipe etc complete all as specified and as directed. 340.00 RM
235 Supply and fix LED street light fittings pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having IP65 protection and impact resistance of IK07 complete and all standard accessories of capacity 35 Watt LED including necessary fixing arrangements, necessary connection etc all as specified and directed. Make: Havells item description ENDURACTYLITEPLATPLUSSL 35WLED757SASYBOPC or equivalent make as given in Appx 'C". 12.00 Each
236 Supply and fix LT junction box for street light, sheet moulding compound (SMC) type with hinged type door and locking arrangement, off white colour, of size 250x150x100 mm (internal) comprising 10Amps MCB ,01 No. bakelite base neutral link and 01 No. earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs including fixing arrangements including wiring from junction box to street light fitting alongwith 2x2.5sqmm+1x1.5sqmm earth wire of FR PVC insulated copper conductor, single core cable in surface /recessed as required in steel conduit complete all as specified and directed. 12.00 Each
237 Supply, installing, testing and commissioning, weather, dust and vermin proof Feeder Piller box factory made, outdoor type of suitable size so as to accommodate the following accessories, depth not less than 500 mm, IP 54 and all as per IE rules, prewired and fabricated with 3.15 mm thick CRCA sheet exoxy power coated double door with aprons, duty powder coated mounted on MS angle iron frame 50 x 50 x 6 mm welded in shape with two coats of synhetic enael paint over a coat of red oxide primer including necessary goruting in PCC 1:3:6 type C-1 using 20 mm graded coare stone aggregates complete with leg 50 cm gounted in ground in PCC at 40 cm above grounded including connection cable with cable glands, lugs etc and consisting of the following :- Note : PCC plinth will be measured and paid separately. 1.00 Each
238 (a) 4 pole MCCB 63 Amps 16 KA - 01 No (including)
239 (b) On load change over switch MCCB type 63 Amps, 4 pole, 415 V (incoming)
240 (c) 4 pole MCB 32 Amps 10 KA - 02 Nos (Outgoing)
241 (d) Bus bars of copper strip of 200 Amps current rating suitable for panel TPN - 1 Set
242 (e) RYB LED indication with selector switch- 1 Set
243 (f) Digital Ammeter 0 to 100 Amps with selector switch- 1 No.
244 (g) Digital Voltmetear 500 Volts with selector switch- 1 No.
245 h) DOL Strater for 3/5 HP motor - 02 Nos
246 Supply and installed testing commisioning of non clog Sewage submersible horizontal type pump sets electrical driven 3 phase, 415V, 50 HZ capacity (discharge-600 LMP, Head-10M & RPM 1440) including 3 phase submersible pump control panel (to be fixed on existing panel board) of suitable capacity and unarmoured flat copper cable 3 x 4 Sqmm multistranded form control panel to submersible motor complete all as specified and directed by Engr-in-charge. Make : Crompton model No CCPM32 or Equivalent of approved make.. 2.00 Each
247 Supply installation, testing and commissioning of Diesel engine dreven generating set with AMF panel 5 KVA 3 Phase 415 Volts 1500 RPM 4 Wire 50 cycles and Power factor 0.8 complete silencer and Acoustic enclosure for sound less mode (sound level not exceeding level specified by central pollution control board) and comprising of the following :- 1.00 Each
248 (A) PRIME MOVER :- Suitable for driving 5 KVA Alternator wate cooled battery start diesed Engie of adequate capacity BHP confirming to BSS 649 and fuel tank suitable for 12 hrs runnig capacity mounted on MS frame pedestal supported with antivibration mounting rated for continuous runnig capable of taking 10 % over load for one hour in any 12 hor operation complete taking into consideration duration due to altitude/temp & complete with the following standard accessories :- Make : Kirloskar/ Cummins/ Cormpton Greaves/ Standard.
249 (a) On load change over switch MCCB type 63 Amps, 4 pole, 415 V (incoming)
250 (b) Fly wheel to match with the flexible coupling
251 (c) Air cleaner oil bath type/Dry type
252 (d) Lubrication oil filter, Fuel filter paper elemet type
253 (e) Blower type fan and radiator
254 (f) Govrnor for class "A" Governing as per IS- 1601 of DS 649/1958
255 (g) Starter, Motor for elecrtric start complete with dynamo alternator, lead acid batteries heaby duty of adequate size, Nos & capacity as reqd with copper conductor leads of adequate size and length not less than 2M including battert box all as directed.
256 (h) Hour meter and RPM Indicator
257 (j) Exhaut pipe brought outside the bldg and lagging of entire length of exhaust pipe with 12 mm dia asbestos rope/Rock wool
258 (k) Instrument panel duly wired comprisig the following
259 (l) Lube oil pressure guage
260 (m) Battery charge indicatior meter
261 (n) Starting switch with Key
262 (B) ALTERNATOR :- 5 KVA at 0.8 PF BRUSHLESS Self excited, self-regulated 3 PHASE 50 Hz 415 V 1500 RPM 4 wire screen protected dri proof free from stimulation provlems continuous rating confirming to BS 2613 complete with automatic voltage regulator O/P voltage regulated between +/- 5% or set voltage from no load to full load.
263 (C) AUTOMATIC MAINS FALURE PANEL :- AMF panel for 5 KVA DG set fabricated out of sheet steel factory made suitable for floor mounting, hinged form panel for easy accessibility with suitable rated bus bar internal wiring and with provision for connectioing incoming/outgoing leads with the following accessories.
264 (a) Auxillary contactors with Timer (On delay)
265 (b) Voltmeter digital with selector switch
266 (c) Ammeter digital with selector switch
267 (d) Frequency meter digital type
268 (e) Power factor meter digital type
269 (f) KWH meter electronic digital type
270 (g) One set of indicator lamps 3 Nos
271 (h) Master switch for Auto/Mannual/Test/Off
272 (j) One set of lamps for indicating "load on set" load on mains "set fails to start" "low oil pressure" " High cylinder temp" "Battery low"
273 (k) Alarm/Hooter
274 (l) Battery charger conneted to main supply side to charge batteries comprising the following :-
275 (i) Transformer of adequate capacity with Auto-cut facilities
276 (ii) DC Ammeter & Voltemeter
277 (iv) Charge rate selection for tricle or high cherge
278 (v) Indicator lamp for Battery
279 (vi) Set of easilly accessible control fuses
280 (vii) Set of relays to Auto-start the engine on Main failure and low voltage
281 (viii) Over/under Voltage relay
282 (ix) Change over switch interior type of suitable capacity
283 (x) Reverse power supply relay
284 (xi) Emergency trip
285 Note :- (1) All fittings/fixtures are also deemed to be included above which are necessary for its proper functionings. (2) Necessary foundation for istallation of DG set shall be provided as per manufacutes recommendations and cost deemed inclusive of the rate quoted above. (3) All testing equimpments are to be arranged and testing carried out by contractor at his own risk.
286 (Pumping Main )
287 Supply, laying, jointing & testing DI-K9 class with spigot and socket, suitable for Push on rubber joint, with internal cement mortor lining, and external zinc and black bitumen coated pipes in any lengths conforming to IS:8329-2000 including Gasket & joints as per IS:9523-2000 laid in trenches/ Road/ Ducts/ Footpath/ on wall/ on floor at locations for 250 mm bore dia complete all as specified and directed. Note :- D I fittings required shall be measured and paid separately. 65.00 RM
288 Supply, laying, jointing & testing DI-K9 class with spigot and socket, suitable for Push on rubber joint, with internal cement mortor lining, and external zinc and black bitumen coated pipes in any lengths conforming to IS:8329-2000 including Gasket & joints as per IS:9523-2000 laid in trenches/ Road/ Ducts/ Footpath/ on wall/ on floor at locations for 200 mm bore dia complete all as specified and directed. Note :- D I fittings required shall be measured and paid separately. 15.00 RM
289 Supply, laying, jointing & testing DI-K9 class with spigot and socket, suitable for Push on rubber joint, with internal cement mortor lining, and external zinc and black bitumen coated pipes in any lengths conforming to IS:8329-2000 including Gasket & joints as per IS:9523-2000 laid in trenches/ Road/ Ducts/ Footpath/ on wall/ on floor at locations for 150 mm bore dia complete all as specified and directed. Note :- D I fittings required shall be measured and paid separately. 15.00 RM
290 Supply, laying, jointing & testing DI-K9 class with spigot and socket, suitable for Push on rubber joint, with internal cement mortor lining, and external zinc and black bitumen coated pipes in any lengths conforming to IS:8329-2000 including Gasket & joints as per IS:9523-2000 laid in trenches/ Road/ Ducts/ Footpath/ on wall/ on floor at locations for 100 mm bore dia complete all as specified and directed. Note :- D I fittings required shall be measured and paid separately. 15.00 RM
291 Supply, fixing & jointing complete CI/DI fittings suitable for DI K-9 class piping such as bends, tapers any type, tee pieces, collars, caps, etc.complete as required as per site for K-9 DI piping spigot & socket ends, flanged ends etc. of size 200 mm to 300 mm complete. 1640.00 KG
292 Supply, fixing & jointing complete CI/DI fittings suitable for DI K-9 class piping such as bends, tapers any type, tee pieces, collars, caps, etc.complete as required as per site for K-9 DI piping spigot & socket ends, flanged ends etc. of size up to 150 mm complete. 1570.00 KG
293 Supply, install, testing and commissioning of 250mm sluice valve of class PN-1.6 double flanged cast iron type with SS spindle, gun metal control nut, non rising type and cast iron wheel head both end flanged IS-2906/14846 marked complete with neoprene rubber gasket, nuts, botls (high tensile) & washers complete all as specified and directed . 1.00 Each
294 Supply, install testing and commissioning of 250mm non return valve of class PN-1.6 including nuts, botls (high tensile) & washers complete all as specified and directed . 1.00 Each
295 Supply, install testing and commissioning of 80mm sluice valve of class PN-1.6 double flanged cast iron type with SS spindle, gun metal control nut, non rising type and cast iron wheel head both end flanged IS-2906/14846 marked complete with neoprene rubber gasket, nuts, botls (high tensile) & washers complete all as specified and directed . 1.00 Each
296 Supply, fixing and jointing Kinetic Double Orifice type Air Valves type PN-1, 50 mm dia combined with screw down isolating valve, small orifice elastic ball resting on a gun metal orifice nipple, large orifice vulcanite ball seating on moulded seat ring, with built-in kinetic features, isolating sluice valve mounted in horizontal portion and operated by wheel gearing, inlet face and drilled, including Reflux valve, butterfly valve & sluice valve complete for size 50 mm dia all as specified and directed . 1.00 Each
297 Fabricate, supply & install in position shaft for air valve with & including 6 mm thick MS pipe shaft 2.70 m long over branch flanged of air valve tee, PCC block of M-150 concrete 150 mm thick around the air valve tee including encasing of verticle shaft in PCC M-150 as shown on drawing in the type of design together with and including making flange joints 200 mm to 400 mm dia pipes, complete as per type/design as approved by GE and as directed. 1.00 Each
298 M& L for construction of valve pit of size 120x120x150 cm internal dimensions with 100 mm thick PCC 1:4:8 type D2 (using 40 mm graded broken stone aggregate) sub base of floor, 50 mm PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) in floor finished even and fair without using extra cement, one brick thick brick work in CM 1:4 , 15 mm thick plaster in CM 1:4 including 3.15 mm thick MS sheet pit cover fixing with angle iron frame 50x50x6 mm thick complete with locking arrangement having provision of lifting handle including 2 coats of synthetic enamel paint over one coat of red oxide primer to steel surface and excavation in soft/loose soil, returning filling and removal of surplus soil up to 50 m distance complete and all as specified and as shown on TD drawing No CEPZ/93/TD/20M Sheet No 1/1. 2.00 Each
299 (Treated Water Supply)
300 Supply, install, testing & commissioning of centrifugal pump sets, electric driven, 3 phase, 415 volts, 50 HP capacity (dischagre-2812.5 LPM & Head 48meter, RPM 2900) including star delta starter (to be fixed on existing panel) of suitable capacity and copper cable 10 sqmm 3 core multistranded two runs from starter to motor through PVC conduit with proper lugs, timer etc and PCC foundation in PCC 1:2:4 type B-1 using 20mm graded stone aggregate 30cm above floor level as per manufacturer's specification including all necessary accessories like gauges and foot valves etc complete all as specified and directed. Make :- Kirlosker Model NO.DB 80/20 or equivalent make as given in Appx 'C". 2.00 Each
301 Supply, install, testing & commissioning of NON CLOG submersible pump sets, electrical driven, 3 phase, 415V, 20HP capacity (discharge-1000LPM, head 40metre, RPM 2900) including star delta starter (to be fixed on panel board) of suitable capacity and flat copper cable 10sqmm 3core multi stranded from starter to submersible motor two runs complete all as specified and directed. Make: Kirloskar Model No. 15000CW 2P or equivalent or equivalent make as given in Appx 'C". 2.00 Each
302 Supply, laying, jointing & testing of 200mm DI-K9 class pipe with internal cement mortar lining and external zinc and bitumen coated pipes conforming to IS 8329:2000 with spigot & socket pipes, jointed with and including tyton joints with push on rubber gasket complete all as specified and directed. Note :- DI fittings required shall be measured and paid separately. 3550.00 RM
303 Supply, laying, jointing & testing of 100mm DI-K9 class pipe with internal cement mortar lining and external zinc and bitumen coated pipes conforming to IS 8329:2000 with spigot & socket pipes, jointed with and including tyton joints with push on rubber gasket complete all as specified and directed. Note :- DI fittings required shall be measured and paid separately. 200.00 RM
304 Supply, Install Testing & Commissioning of factory made CPRI type tested LT panel board out door type, hood on top, weather, vermin proof, platform mounted suitable for 415V, 3 phase 4 wire 50Hz AC supply system all as specified and directed, with necessary bus bar arrangement with insulated copper bus bar 300Amps rating installed on porcelain insulators housed in seperate bus chambers covered with heat shrinkable sleeves with necessary bus bar tappings, copper control wiring of required size, the panel shall be dust and vermin proof, IP-54 class protection and made of 3mm CRCA sheet with 40x40x6mm angle iron frame, angle iron support of 40x40x6mm with 0.6mm above ground level and 0.4m grouted in ground /PCC floor with necessary earth work excavation, hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) and duly powder coated on the outside and inside including provison of PCC platform 100mm thick with PCC 1:4:8 type D-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent chambers to accomodate complete all as specified and directed including the following accessories: (a) Bus bars of copper strip of 300Amps TPN-01 No (b) 4 pole MCCB 200Amps 25KA-01 No(incoming) (c) 4 Pole MCCB 100 Amps 16KA-02 No (outgoing) (d) 4 pole MCCB 40 Amps 16KA-03Nos(outgoing) including 01 spare (e) Single phase preventer for 50HP pump motor set-02 Nos & for 20 HP motor pump set -02 Nos (f) Mains indicating lamps with selector switch RYB -01 Set (g) Digital ammeter 0 to 200Amps with selector switch (h) Digital voltmeter 500V with selector switch. (j) Space for providing star delta starter for 50HP motor pump set -02 Nos & for 20 HP motor pump set-02 Nos 1.00 Each
305 M & L for Ductile iron fittings upto 200mm for spigot and socketed pipes bends (any type, radius and angle), tapers any type (straight, bend, incresing, decreasing or double socket etc.), Tee piece, single branch 'Y'junction double branch, collar etc., caps and plugs etc. as per IS: 9523 complete all as specified and directed. 550.00 Kg
306 S&F cast iron air valves with two air outlets conforming to IS-14845 of size 50mm dia bore and fixing up in ductile iron water supply mains of size 200mm dia complete with provision of 50mm dia CI body, brass spindle sluice valve & jointing etc. all as specified and directed. 1.00 Each
307 Material and labour for machinery valve chamber size 900mmx900mmx900mm of internal dimension, PCC solid block masonry chamber 200mm thick(valve chamber) built in CM 1:6, PCC 1:2:4 type B-1, 100mm thick in floor, 15mm thick plaster in CM 1:4 on internal/external surface, PCC 1:3:6 type C-1, 75mm thick as in coping, MS sheet cover 3.15mm thick with angle iron 50x50x5mm, flat iron hold fast of 15mmx4mm including locking handle 6mm dia 30cm long, applying with 2 coats of synthetic enamel paint over one coat of red oxide primer on all metal works complete all as specified and directed including necessory excavation and earthwork complete. 2.00 Each Job
308 Material and labour for machinery valve chamber size 1200mmx1200mmx1000mm of internal dimension, PCC solid block masonry chamber 200mm thick(valve chamber) built in CM 1:6, PCC 1:2:4 type B-1, 100mm thick in floor, 15mm thick plaster in CM 1:4 on internal/external surface, PCC 1:3:6 type C-1, 75mm thick as in coping, MS sheet cover 3.15mm thick with angle iron 50x50x5mm, flat iron hold fast of 15mmx4mm including locking handle 6mm dia 30cm long, applying with 2 coats of synthetic enamel paint over one coat of red oxide primer on all metal works complete all as specified and directed including necessory excavation and earthwork complete. 2.00 Each Job
309 M&L for boring holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 250mm dia suitable for 0.4mm mpa working pressure complete all as specified and directed. 50.00 RM
310 Supply, laying, jointing, testing and commissioning of HT XLPE under ground cable suitable for earthed system 22KV 'E' grade, 3 core 120Sqmm, XLPE insulated round wire armoured aluminium conductor, ISI marked laid in trenches or through GI pipe laid under floors, road etc fixed concealed in walls encased in GI pipe etc complete all as specified and as directed. 30.00 RM
311 Supply and fix cable end kit for 22KV (Earthed) grade cable for outdoor termination, heat shrinkable type joint complete with jointing material and accesorries suitable for HT, XLPE armoured aluminium conductor cable of size 3 core 120 Sqmm complete all as specified and directed. 2.00 Each
312 Supply and install perforated MS cable trays of size 450mm width x 50mm depth x 1.6mm thickness, including horizontal and verticle bends, reducers, tees, cross members duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and other accessories as required, duly suspended from ceiling with and including MS suspenders (10mm dia threaded rod, anchor fasteners and angle of 40x40x5mm thick) complete all as specified and as directed. 50.00 RM
313 Supply and install perforated MS cable trays of size 300mm width x 50mm depth x 1.6mm thickness, including horizontal and verticle bends, reducers, tees, cross members duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and other accessories as required, duly suspended from ceiling with and including MS suspenders (10mm dia threaded rod, anchor fasteners and angle of 40x40x5mm thick) complete all as specified and as directed. 50.00 RM
314 Supply and install perforated MS cable trays of size 150mm width x 50mm depth x 1.6mm thickness, including horizontal and verticle bends, reducers, tees, cross members duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and other accessories as required, duly suspended from ceiling with and including MS suspenders (10mm dia threaded rod, anchor fasteners and angle of 40x40x5mm thick) complete all as specified and as directed. 50.00 RM
315 (Miscellaneous B/R and E/M works)
316 Providing and making necessary arrangments for dewatering and disposal including arranging pumpsets etc. complete from excavated trenches of any depth and description but not exceeding 6m deep of exccavation complete all as specified and directed. 1740.00 Per Hour
317 150mm thick (compacted thickness) WMM in single layers with laying, spreading (with paver finisher only) and compacting base course of graded stone aggregate and granular material conforming to MORT&H specifications (Table 400-II) in layers of equal compacted thickness each, consolidated, including pre-mixing the material with water at OMC in mechanical mixer (Pug Mill), carriage of mixed material by tippers to site, laying in uniform layers in base course on a well prepared sub-base/base course and compacting with power vibratory-roller to achieve the desired density complete as per MORTH specification clause-406 including all material, labour, machinery, lighting, guarding and maintenance of diversion complete all as specified and directed. 120.00 10Sqm
318 S&F precast manhole covers heavy duty including outer frame and set in CM 1:6 complete all as specified and directed. 300.00 Each
319 Supply and fix Energy efficient ceiling fan of 1200 mm (48") sweep BEE 5 star rated high speed low poer consumption superior aluminium bladesand provn of 3 core flexible copper conductor cable of size 23/0.19 from ceiling rose to ceiling fan complete all as specified and directed . confirming to Cat Part No- KASSELS STAR of make- Bajaj of equivalent in Crompton. 8.00 Each
320 S & F LED tube light fitting wall mounted 18 watt 230 Volt 6500K with opal whitw polycabonate defuser provided with high efficient integral constan currenet LED driver 230 v etc. complete with mounting batten including all accessories internally prewiredand including connecting up with twin core twisted flexible copper conductor cable with suitable size from ceiling rose to connector confirming to Cat Part No-BLRB DB 118 & BLRB18 W CW LED make: Bajaj or equivalent in Philips or Havells. 29.00 Each
321 S & F MCB SP 240 volts 6 to 32 Amps 10 KA complete all as specified and directed. 36.00 Each
322 S & F MCB SPN 240 Volts 32 Amp 10 KA complete all as specified and directed. 5.00 Each
323 S & F MCB TPN 40A, 415, 10 KA complete all as specified and directed. 1.00 Each
324 S & F blanking plate of PVC made complete all as specified and directed. 5.00 Each
325 Supply and fix air circulator wall mounted Fans of sweep 600 mm , 1440 RPM, single phase, 200 W with Air delivery of capacity 250 CMM 3 speed. Item code NO: 250528 Make Bajaj Supreme Plus or equivalent make as given in Appx 'C". complete all as specified and directed. 6.00 Each
326 S & F exhaust fan, with louvers, single phase, heavy duty, PVC, 230 mm sweep, 1400 RPM including fixing of mounting frame in the round hole cutting in the wall, by means of rugged bolts, nuts and washers etc, including three core copper conductor flexible cord of 0.5 Sqmm cross sectional area of required length from ceiling rose to the porcelain connector block of the exhaust fan complete all as specified and directed. 3.00 Each
327 S & F exhaust fan, with louvers, single phase, heavy duty, 300 mm sweep, 50 Hz, 1400 RPM including fixing of mounting frame in the round hole cutting in the wall, by means of rugged bolts, nuts and washers etc, including 3 core copper conductor flexible cord of suitable size of required length from ceiling rose to the porcelain connector block of the exhaust fan complete all as specified and directed. Make : Bajaj, Item code -70068 SUPREME PLUS or equivalent make as given in Appx 'C". 9.00 Each
328 Supply and fix LED energy efficient flood light 120 watt Luminaire in pressure die cast housing for efficient dissipation of heat and anodized aluminium reflector with IP 66 protection and heat resistant toughened glass with 5 KV in built surge protector and 10 KV external surge protector as per make : Bajaj Cat Part No. BJFL 120 W LED I or equivalent make as given in Appx 'C". complete all as specified and directed. 7.00 Each
329 S & F LED Energy Efficient security light fitting 25 watts LED pressure die cast aluminium housing in heat resistant glass cover with IP 65 protection and including GI pipe as require length and size with fixing accessories complete all as specified & directed complete with M & L for fixing / mounting bracket, clamps, nuts, bolts, washers etc. Make : Baja Cat Part No: BCLST 25 W LED I V2 or equivalent make as given in Appx 'C". 7.00 Each
330 M& L for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick, buried vertically in ground (Earth pit not less than 2.25 metres deep below normal ground level and top edge of the plate not less than 1.5 m below ground level), connected to and including GI strip 32x6 mm as earthing lead by means of bolts, nuts & checknuts and washers of galvanized iron or steel drawn through GI pipe 40 mm dia medium grade pipe for protection of G.I earth strip, both to be provided to the extent of 7.5 metres, all as shown on electrical plate No 3 of MES SSR-2009 Part-I, other end connected to electrical main switch board (inside the bldg) GI protection pipe buried in ground, laid under floors/plinths or fixed on walls or concealed in walls etc; with provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate , including PCC 1: 2 : 4 type B-2 earth pit with precast RCC cover in CC 1:2:4 type B1 including 10mm dia deformed bars @100mm C/C with handle , with G.I 20 mm dia medium grade pipe for watering and M.S funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of strata & testing on completion complete all as specified and as directed. 44.00 Each
331 M&L for earthing with GI plate 600mm x 600mm x 6mm thick, burried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 Mtr below normal ground level, connecting to galvanized iron or steel earth wire 4.0mm dia (NO.8 SWG) upto 7.5 Mtr long from earth point to test point by means of bolts, nuts, check nuts, washers and provision of charcoal, salt etc including watering arrangement with 20mm dia GI pipe, 15mm dia light grade pipe for protection of GI strip upto 7.5 mtr, MS funnel, PCC chamber in cement concrete 1:3:6 type C1 and finished even and smooth without using extra cement, 50 mm thick precast RCC cover 1:2:4 type B1 including 10 mm dia deformed bars @100 mm c/c on both ways for full size of chamber complete all as per electrical plate No 3 including necessary excavation and earth work in any type of soil complete all as directed. 7.00 Each
332 PHASE-II :(Schedule 'A' Part-XVI: Manning and Operation of Sewage Treatment Plants) (For Ist year from next day of completion of Phase-I Work)
333 Out sourcing for Manning and operation of Sewage Treatment Plant of 3 MLD capacity round the clock, by deploying total 3 FGM (Skilled) per day ( One FGM for one shift of 08 Hrs) including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by logging of runing records, upkeep of installation consisting of STP, Pumping sets, DG set, Air compressor, Chlorination plant, Sluice valves and reporting the occurance at the installation on all working days including Sunday and Holidays complete all as directed. 365.00 PER DAY
334 Out sourcing for Manning and operation of Sewage Treatment Plant of 3 MLD capacity,in one shifts per day, by deploying 01 Helper (Un-Skilled) per shift of 08 Hrs each including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by assisting the FGM in operation of chlorine dosing , application of culture for development of bacteria in fab reactor and controlling the delivery of treated water output at water points of STP installation area including operating treated water installation from STP for gardening of nearby locations and cleaning installation premises with in a radius of 3m from the installation area on all working days including Sunday and Holidays complete all as directed. 365.00 PER DAY
335 PHASE-II (Contd) :(Schedule 'A' Part-XVI: Manning and Operation of Sewage Treatment Plants for IInd year)
336 Out sourcing for Manning and operation of Sewage Treatment Plant of 3 MLD capacity round the clock, by deploying total 3 FGM (Skilled) per day ( One FGM for one shift of 08 Hrs) including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by logging of runing records, upkeep of installation consisting of STP, Pumping sets, DG set, Air compressor, Chlorination plant, Sluice valves and reporting the occurance at the installation on all working days including Sunday and Holidays complete all as directed. 365.00 PER DAY
337 Out sourcing for Manning and operation of Sewage Treatment Plant of 3 MLD capacity,in one shifts per day, by deploying 01 Helper (Un-Skilled) per shift of 08 Hrs each including Saturday, Sunday and Holidays complete all as specified and as directed. The outsourcing of services including running of sewage treatment plant by assisting the FGM in operation of chlorine dosing , application of culture for development of bacteria in fab reactor and controlling the delivery of treated water output at water points of STP installation area including operating treated water installation from STP for gardening of nearby locations and cleaning installation premises with in a radius of 3m from the installation area on all working days including Sunday and Holidays complete all as directed. 365.00 PER DAY
338 Note for BOQ item No - 16.01 to 16.05 : a) The contractor shall quote the rate for Manning and Operation only. Replacing of defective electromechanical parts, providing spares and maintenance of Sewage Treatment Plants and allied equipments during the period of 2 years (Defect Liability Period) from satisfactory completion of Phase -I shall be covered under Defect Liability Period.
339 b) As per Govt policy, adequate amount of insurance of all the workers shall be made against any accident before commencement of the work without extra cost to the department.
340 c) The work order of outsourcing for M & O shall be placed by GE & no price adjustment during whole period due to change in minimum fair wages shall be admissible.
341 d) The STP will be operated for 24 hours per day, unless otherwise specified by the Engineer-in-Charge / GE. Necessery recovery will be made for non operation of plants per shift at the proportional rate and the same shall be final and binding.
342 e)The operator being deployed in the work shall have minimum qualification of ITI with 02 years experience in the relevent field for FGM and Helper should be 10th pass with 02 years experiance in relevent field. Necessary qualification certificate and experiance certificate shall be produced for verification of Engineer-in-Charge & get the approval before deploying for works.
343 f) Proper and effeicient functioning of the plant must be ensured through regular inspection by qualified Engineer bi-monthly preferably by OEM or by his authorised agency.
344 g) The contractor shall carry out routine maintenance as per procedure mentioned in the PS.
345 h) Staff deployed by the contractor shall carry out daily careful cleaning of the inside installation, greasing of pump, motors, panel boards, DG sets and internal portion of pump house building , 3m external portion , 3m in radius for outdoor panel boards and maintain installations in presentable condition all time all as specified and as directed.
346 j) The contractor shall carryout routine check and maintain check sheet daily, weekly, monthly and upkeep the installation , rectify normal trouble shooting, replacement of gland packing of pumps and sluice valves in installations and minor parts like nuts, bolts, washers, coupling rubber, star packing etc. without extra cost to the deparment.
347 k) Contractor will maintain log sheet daily and submit to department duly completed along with attendance sheet and payment register.
348 l) No T & P will be issued by the department for doing the above work, it shall be arranged and provided by the contractor like PH testing kit, chlorine test kit, turbidity test kit, pipe wrench, screw drivers, sluice valve opening /closing kit, cutting plier, digging tools etc.
349 m) The contractor shall check and implement all the labour laws/precautions for health and safety of labour /OEM operator working in hygenic conditions.
350 n) The contractor shall be get the testing of treated sewage from approved test laboratory ( NABL certified or state PCB approved) and keep records duly signed by Engineer-in-Charge as per interval of 3 months to ascertain result of treated sewage all as per requirement given in particular specification here-in-after. Expenditure for the same shall be borne by the contractors and is deemed to be included in quoted rates.
351 o) During Manning & Operation, if the personal is absent from the duty, recovery shall be effected at the double the rates worked out from quoted rates at the proportional basis. For that purpose, proper duty roster and attendance register shall be maintained and signed by the Engineer-in-Charge. These item will be operated only when the plant is running satisfactorily & No payment will be made in case he plant is unserviceable due to any cause.
352 p) The rates quoted by the contractor shall be inclusive of proper uniform of technician/operator as directed by GE.
353 q) Salvage materials/sludge obtained after treatment shall be disposed off outside defence land as per local civil authorities laid down rules.
354 r) The contractor shall also be responsible for periodical cleaning of screens removal and disposal of screens material to a place outside defence land.
355 s) All consumables/chemicals like Sodium Hypo Chlorite, Dewatering Poly Electrolyte and Aerobic type bioculture powder for development of bacteria shall be paid separately as Supply only items as mentioned in BOQ here-in-after on required/consumption basis as certified by Engineer-in-charge/GE.
356 Supply only Sodium Hypo Chloride @6% concentration for treatment of water complete all as specified and as diretced. 73200.00 Litre
357 Supply only triple floc Poly Electrolyte white powder having pH value 5-8 complete all as specified and as diretced. 660.00 Kg
358 Supply only superior quality alum in powder form for treatment purpose complete all as specified and as diretced. 3660.00 Kg
359 Supply only Aerobic type Bioculture powder for development of bacteria and reduces BOD and COD, suppresses foul odour from STP complete all as specified and as diretced. 200.00 Kg
360 Note for Item No 16.24 to 16.27:- The above qualtities of consumable to be incorporated during outsourciing for M & O of STPs for two years period. The rates for these items are aplicable for both years of M & O and no claims for any change in rates shall be admissible for these items duriing this period. The procurement schedules of these items shall be as decided by the Engineer-in-Charge/GE.
Tender InquiryInquiry